Duct Size Calculator

Cubic feet per minute required
Typical residential: 0.06 – 0.10
Residential trunk: 700-900, branch: 600

Close-up of various hand tools including wrenches and pliers on a dark surface.

Photo by Nishant Aneja / Pexels

How Duct Sizing Works

Correct duct sizing balances three factors: delivering enough airflow (CFM), keeping air velocity low enough to avoid noise, and maintaining acceptable static pressure loss (friction rate) so the blower can push air through the system.

Close-up of various hand tools including wrenches and pliers on a dark surface.

Photo by Nishant Aneja / Pexels

The Equal Friction Method

The most common residential approach sizes every duct run to the same friction rate (pressure drop per 100 feet). Typical values are 0.06 to 0.10 inches of water gauge per 100 ft. This calculator uses a simplified form of the Darcy-Weisbach equation calibrated to standard galvanized steel duct.

Close-up of various hand tools including wrenches and pliers on a dark surface.

Photo by Nishant Aneja / Pexels

Round vs. Rectangular

Round ducts are the most efficient shape -- they have the lowest surface area for a given cross-section, meaning less friction loss and material cost. Rectangular ducts fit into tight spaces but should be kept to a 4:1 aspect ratio or less (2:1 preferred) to maintain good airflow distribution.

Close-up of various hand tools including wrenches and pliers on a dark surface.

Photo by Nishant Aneja / Pexels

Equivalent Diameter

A rectangular duct's equivalent round diameter is the round duct size that produces the same friction loss at the same airflow. The formula is:

Deq = 1.3 × (W × H)0.625 / (W + H)0.25

Close-up of various hand tools including wrenches and pliers on a dark surface.

Photo by Nishant Aneja / Pexels

Quick Reference

CFMRound (in)Typical Use
1006Single room branch
2007-8Large room branch
40010Small trunk
80012-14Main trunk
120016Large main trunk
2000+18-20Commercial trunk